Installing a physical Tanium Appliance in a datacenter
Follow the steps in this topic to rack a physical Tanium Appliance and configure its iDRAC interface and IP address.
Before you begin, review the specifications of the physical Tanium Appliance, particularly the environmental requirements and physical characteristics, to ensure that the location you selected in your datacenter supports the requirements of the Appliance.
Contents of the box
-
Ready Rails mounting kit
-
Power cords:
-
Small or Medium: C13 to either NEMA 5-15P or C14 plugs
-
Large or Extra-Large: C19 to C20
-
-
Hardware manual
-
Tanium Hardware Addendum
-
Optical transceivers (if the Tanium Appliance was purchased with the fiber network option):
-
Small or Medium: Short-range SFP+
-
Large or Extra-Large (v3): Short-range SFP+
-
Large or Extra-Large (v4): Short-range SFP28
-
What you need to provide
-
Server rack or cabinet
-
Two power outlets:
-
Small or Medium: NEMA 5-15P wall receptacles or C13 PDU receptacles
-
Large or Extra-Large: C19 PDU receptacles
-
-
Two Ethernet cables with appropriate switch connections:
-
Copper option: RJ45 Ethernet cables adequate to support 10GbE
-
Fiber option—one of the following:
-
Duplex LC fiber optic cables ((supports 10GbE with included SFP+
short-range optics for Small or Medium; supports 25GbE with included SFP28 short-range optics for Large or Extra-Large)
-
SFP28 twinax DAC (Large or Extra-Large v4 only; supports 25GbE)
-
SFP+ twinax DAC (supports 10GbE)
-
Note: Additional cables and connections might be required for more advanced network configurations. Tanium Support provides guidance if that is necessary. -
-
• One RJ45 Ethernet cable adequate to support 1GbE for iDRAC
-
• KVM console
-
• Network settings (fixed IPv4 addresses, subnet mask, and default gateway for NICs and iDRAC interface)
Information tag
The information tag is a slide-out label panel on the front of the chassis. This panel contains identifying information, such as the SKU and serial number (service tag).
Physical connections
Small/Medium (v4)
The small/medium (v4) Appliance has the following ports for use with deployment:
|
|
Network interface A1 |
|
|
Network interface A2 |
|
|
iDRAC network port |
|
|
USB ports for KVM |
|
|
Network interface B1 |
|
|
Network interface B2 |
|
|
VGA for KVM |
|
|
Power 1 and Power 2 C14 inlets (support locking C13 plugs) |
Small/medium (v3)
The small/medium (v3) Appliance has the following ports for use with deployment:
|
|
VGA for KVM |
|
|
iDRAC network port |
|
|
USB ports for KVM |
|
|
Network interface A1 |
|
|
Network interface A2 |
|
|
Network interface B1 |
|
|
Network interface B2 |
|
|
Power 1 and Power 2 C14 inlets (support locking C13 plugs) |
Large/extra-large (v4)
The large/extra-large (v4) Appliance has the following ports for use with deployment:
|
|
Network interface A1 |
|
|
Network interface A2 |
|
|
Network interface A3 |
|
|
Network interface A4 |
|
|
Power 1 C20 inlet (supports locking C19 plug) |
|
|
Network interface B1 |
|
|
Network interface B2 |
|
|
Network interface B3 |
|
|
Network interface B4 |
|
|
iDRAC network port |
|
|
USB ports for KVM |
|
|
VGA for KVM |
|
|
Power 2 C20 inlet (supports locking C19 plug) |
Large/extra-large (v3)
The large/extra-large (v3) Appliance has the following ports for use with deployment:
|
|
Power 1 C20 inlet (supports locking C19 plug) |
|
|
iDRAC network port |
|
|
USB ports for KVM |
|
|
Network interface A1 (fiber option only; copper option has only two interfaces on this card) |
|
|
Network interface A2 |
|
|
Network interface A3 |
|
|
Network interface A4 (fiber option only; copper option has only two interfaces on this card) |
|
|
Network interface B1 |
|
|
Network interface B2 |
|
|
Network interface B3 |
|
|
Network interface B4 |
|
|
VGA for KVM |
|
|
Power 2 C20 inlet (supports locking C19 plug) |
Installation and bootstrap configuration
Install and connect the Tanium Appliance
Power on the Appliance and configure the iDRAC interface
Use these steps to configure the iDRAC interface. With these steps, you set up the tanremote user account, which can be used to complete the initial configuration later.
-
Power on the Appliance.
The boot and start-up processes take a few minutes.
-
When prompted to sign in, specify the user name tanadmin and the default password Tanium1.
CODE------------------------------------------------------ >>> Initial Configuration <<< Initial configuration workflow for a new TanOS Appliance. All items must be complete before the Appliance can be used. Keymap: us IP Address: Hostname: initial-tanos-347587.localdomain FIPS 140-3: disabled M: Toggle FIPS 140-3 Mode P: Set Password (INCOMPLETE) I: Configure iDRAC Set the password to continue configuration F: [DISABLED] Finish Initial Configuration S: Shutdown Z: Log out ------------------------------------------------------ TanOS Version: 1.9.0 Please select: -
Enter I (Manage iDRAC).
-
Enter N to go to the Configure iDRAC Network screen.
-
Follow the prompts to configure the iDRAC network.
CODE>>> Initial Config -> Manage iDRAC - > Configure iDRAC Network <<< > These configuration settings will be applied to the iDRAC interface. iDRAC user configuration can be performed in the user administration menu. Current iDRAC settings: IPv4 Address: IPv4 Gateway: IPv6 Address: ::/64 IPv6 Gateway: Would you like to continue with iDRAC IP configuration? [Yes|No]: yes Enter the IPv4 address/prefix (e.g. 10.2.3.4/24): 10.10.10.65/24 Enter the IPv4 gateway address (e.g. 10.2.3.1): 10.10.10.2 Would you like to accept default IPv6 settings? [Yes|No]: yes New settings: IPv4 Address: 10.10.10.65/24 Default IPv4 Gateway: 10.10.10.2 Manual IPv6 settings: No Are these settings correct? [Yes|No]: yes Configuring iDRAC interface, can take a minute or two ... Press enter to continue -
Enter P and follow the prompts to change the password of the tanremote user.
CODE>>> Appliance Configuration -> Manage iDRAC -> Set iDRAC Password <<< This will change the iDRAC user tanremote password. Access to the iDRAC is via the specific iDRAC IP. Would you like to change the tanremote password? [YES/NO]: yes The password policy requires meeting these rules: - Minimum 10 characters long - Maximum 20 characters long - At least 1 upper case character - At least 1 lower case character - At least 1 numeric character - At least 1 other character - Must not be based on a dictionary word - Must not contain part of the username Please enter password (will not be displayed): -
Ensure you can access the iDRAC virtual console at http://<iDRAC interface IP address>.
-
Ensure you can sign in with user name tanremote and the password that was set with this procedure and then provide the password for the tanremote user to your TanOS administrator so that user can complete the initial configuration.
(Optional) Configure the Appliance IP address
Use these steps to assign an IP address to the Appliance. After performing these steps, you can sign out of the TanOS console and a TanOS administrator can connect through SSH later to resume the full initial configuration.
-
When prompted to sign in, specify the user name tanadmin and the default password Tanium1.
CODE------------------------------------------------------ >>> Initial Configuration <<< Initial configuration workflow for a new TanOS Appliance. All items must be complete before the Appliance can be used. Keymap: us IP Address: Hostname: initial-tanos-347587.localdomain FIPS 140-3: disabled M: Toggle FIPS 140-3 Mode P: Set Password (INCOMPLETE) I: Configure iDRAC Set the password to continue configuration F: [DISABLED] Finish Initial Configuration S: Shutdown Z: Log out ------------------------------------------------------ TanOS Version: 1.9.0 Please select: -
Enter P and then follow the prompts to change the password.
CODE------------------------------------------------------ >>> Initial Config -> Set Password <<< Preparing to change the password for tanadmin The password policy requires meeting these rules: - Minimum of 10 characters long - At least 1 upper case character - At least 1 lower case character - At least 1 numeric character - At least 1 other character - Must not match any of recent 4 passwords - Must not be based on a dictionary word - Must not contain part of the username Please enter password (will not be displayed): Password score: 55 out of 100 (strong) Please enter password again: The password change was successful. Press enter to continueTip: Follow the password policy guidelines closely. Note the password score that appears and aim for a strong password. -
Press Enter to return to the Initial Configuration menu.
CODE------------------------------------------------------ >>> Initial Configuration <<< Initial configuration workflow for a new TanOS Appliance. All items must be complete before the Appliance can be used. Keymap: us IP Address: Hostname: initial-tanos-347587.localdomain FIPS 140-3: disabled M: Toggle FIPS 140-3 Mode P: Set Password (complete) A: Set IP Address (INCOMPLETE) N: Set FQDN (hostname) (INCOMPLETE) D: Set DNS Nameservers (INCOMPLETE) T: Set NTP (time) (INCOMPLETE) E: View and Accept EULA (INCOMPLETE) F: [DISABLED] Finish Initial Configuration S: Shutdown Z: Log out ------------------------------------------------------ TanOS Version: 1.9.0 Please select: -
Enter A, and then follow the prompts to set the static IP address, IPv6 settings, gateway, and advertised Ethernet speeds. The TanOS console confirms that the settings are applied.
CODE>>> Network Configuration <<< > Note: any existing IP address listed below is NOT persistent/DHCP assigned. Please provide a static IP address below regardless of the current configuration. At the end of the initial configuration routine you will be logged out. If the IP address is changed then you will need to modify your connection settings to reach the TanOS menu. Available interfaces: #: Interface State Link MAC IP Location 1: ens160 UP UP 00:0c:29:35:f4:fa 10.10.10.60/24 virtual Please select: 1 Current settings: Interface: ens160 IPv4 Address: 10.10.10.60/24 Default IPv4 Gateway: 10.10.10.2 IPv6 Address: fe80::20c:29ff:fec3:4afa/64 IPv6 Gateway: Advertised Speeds: 1Gbps 10Gbps 25Gbps Enter the IPv4 address/prefix (e.g. 10.2.3.4/24): 10.10.10.60/24 Enter the IPv4 gateway address (e.g. 10.2.3.1): 10.10.10.2 Would you like to accept default IPv6 settings? [Yes|No]: yes Would you like to accept the current Ethernet advertised speeds? [Yes|No]: yes New settings: Interface: ens160 IPv4 Address: 10.10.10.60/24 Default IPv4 Gateway: 10.10.10.2 Manual IPv6: No IPv6 Address: fe80::20c:29ff:fec3:4afa/64 IPv6 Gateway: Advertised Speeds: 1Gbps 10Gbps 25Gbps Are these settings correct? [Yes|No]: yesThe IP address setting changes from incomplete to complete.
-
Provide the IP address and the password for the tanadmin user to your TanOS administrator so that user can access the Appliance using SSH and complete the initial configuration.